Backflow assembly test · 9598 Quarry Ln
ApprovedFiled Aug 28, 2026 by Morgan Calloway, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 28, 2026
- Assembly type
- DC
- Serial number
- B303764
- Size
- 3/4
- Test gauge serial
- G-5395
- Gauge calibration date
- Jun 30, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-53-01277
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9598 Quarry Ln
Owner: Avery Ashby
Parcel 077-53-01277