Backflow assembly test · 167 Old Church Ln
ApprovedFiled Nov 16, 2025 by Taylor Lindqvist, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 16, 2025
- Assembly type
- PVB
- Serial number
- W712343
- Size
- 1
- Test gauge serial
- G-3168
- Gauge calibration date
- May 18, 2025
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Lindqvist, current on the service date
- All required fields present
- Address matches parcel 077-20-01307
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.