Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6033 Meadow Lark Way

Approved

Filed Sep 2, 2025 by Logan Lindqvist, Ridge Backflow Testing · filed from phone

Report

Date of service
Sep 2, 2025
Assembly type
RP
Serial number
A649843
Size
3/4
Test gauge serial
G-6927
Gauge calibration date
Apr 29, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-69-01287
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6033 Meadow Lark Way
Owner: Morgan Pruitt
Parcel 081-69-01287