← Backflow review queue
Backflow assembly test · 2030 Meadow Lark Trl
ApprovedFiled Nov 12, 2023 by Drew Nguyen, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 12, 2023
- Assembly type
- RP
- Serial number
- B560060
- Size
- 3/4
- Test gauge serial
- G-9542
- Gauge calibration date
- Apr 21, 2023
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-88-01043
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2030 Meadow Lark Trl
Owner: Avery Harlow
Parcel 081-88-01043