Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7193 Orchard Trl

Approved

Filed Apr 20, 2025 by Emerson Lindqvist, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Apr 20, 2025
Assembly type
RP
Serial number
W305565
Size
3/4
Test gauge serial
G-9906
Gauge calibration date
Oct 22, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-14-01192
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7193 Orchard Trl
Owner: Jamie Harlow
Parcel 081-14-01192