Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Riverside Diner

Approved

Filed Apr 7, 2025 by Taylor Calloway, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Apr 7, 2025
Assembly type
RP
Serial number
Z357906
Size
4
Test gauge serial
G-8056
Gauge calibration date
Dec 17, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-51-01233
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7145 Fox Run Way
Owner: Marsh Holdings LLC
Parcel 081-51-01233