Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6218 Ridgeview Rd

Approved

Filed Jul 19, 2026 by Emerson Lindqvist, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Jul 19, 2026
Assembly type
RP
Serial number
Z816291
Size
1
Test gauge serial
G-4661
Gauge calibration date
Apr 22, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-38-01312
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6218 Ridgeview Rd
Owner: Morgan Ashby
Parcel 081-38-01312