Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 790 Mill Creek Ct

Approved

Filed Feb 25, 2026 by Logan Lindqvist, Ridge Backflow Testing · filed from phone

Report

Date of service
Feb 25, 2026
Assembly type
RP
Serial number
A508898
Size
1
Test gauge serial
G-3986
Gauge calibration date
Sep 24, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-34-01117
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

790 Mill Creek Ct
Owner: Hayden Stroud
Parcel 081-34-01117