Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Taqueria

Approved

Filed Sep 17, 2026 by Drew Nguyen, Ridge Backflow Testing · filed from phone

Report

Date of service
Sep 17, 2026
Assembly type
RP
Serial number
Z578290
Size
1
Test gauge serial
G-7923
Gauge calibration date
Jun 29, 2026
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-21-01071
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6346 Hickory Rd
Owner: Vance Holdings LLC
Parcel 081-21-01071