Backflow assembly test · 819 Old Church Way
ApprovedFiled Aug 23, 2026 by Jamie Hollins, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Aug 23, 2026
- Assembly type
- RP
- Serial number
- A117061
- Size
- 3/4
- Test gauge serial
- G-6008
- Gauge calibration date
- Jul 1, 2026
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-53-01200
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.