Backflow assembly test · 3196 Fox Run Dr

Approved

Filed Aug 14, 2026 by Sam Calloway, Lakeside Backflow Testing · filed from phone

Report

Date of service
Aug 14, 2026
Assembly type
DC
Serial number
B488606
Size
1
Test gauge serial
G-5283
Gauge calibration date
Oct 26, 2025
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-22-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3196 Fox Run Dr
Owner: Rowan Wexler