Backflow assembly test · 1474 Mill Creek Ct
ApprovedFiled Jun 28, 2024 by Jamie Hollins, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Jun 28, 2024
- Assembly type
- DC
- Serial number
- K207128
- Size
- 1
- Test gauge serial
- G-7152
- Gauge calibration date
- May 7, 2024
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Hollins, current on the service date
- All required fields present
- Address matches parcel 091-66-01266
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1474 Mill Creek Ct
Owner: Riley Calloway
Parcel 091-66-01266