Backflow assembly test · 2803 Cedar Hollow Trl

Approved

Filed Jul 16, 2026 by Jamie Hollins, Clearwater Backflow Testing · filed from phone

Report

Date of service
Jul 16, 2026
Assembly type
RP
Serial number
Z731711
Size
1
Test gauge serial
G-8761
Gauge calibration date
Jan 5, 2026
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Hollins, current on the service date
  • All required fields present
  • Address matches parcel 091-72-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.