Backflow assembly test · 8918 Cedar Hollow Trl

Approved

Filed May 20, 2025 by Cameron Benton, Lakeside Backflow Testing · filed from phone

Report

Date of service
May 20, 2025
Assembly type
RP
Serial number
Z803050
Size
1
Test gauge serial
G-3394
Gauge calibration date
Feb 10, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
1.2 psid
Relief valve opened at
3.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-30-01255
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.