Backflow assembly test · Maple Leaf Bakery

Approved

Filed Oct 15, 2025 by Sam Calloway, Lakeside Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Oct 15, 2025
Assembly type
RP
Serial number
W641017
Size
4
Test gauge serial
G-2502
Gauge calibration date
Oct 23, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Calloway, current on the service date
  • All required fields present
  • Address matches parcel 091-61-01109
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.