Backflow assembly test · Maple Leaf Bakery
ApprovedFiled Oct 15, 2025 by Sam Calloway, Lakeside Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 15, 2025
- Assembly type
- RP
- Serial number
- W641017
- Size
- 4
- Test gauge serial
- G-2502
- Gauge calibration date
- Oct 23, 2024
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Calloway, current on the service date
- All required fields present
- Address matches parcel 091-61-01109
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.