Backflow assembly test · Maple Leaf Bakery

Filed Nov 18, 2026 by Jamie Hollins, Clearwater Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Nov 18, 2026
Assembly type
RP
Serial number
W641017
Size
4
Test gauge serial
G-6474
Gauge calibration date
Jul 26, 2026
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-61-01109
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

5119 Hickory Way
Owner: Danner Holdings LLC
Parcel 091-61-01109