Ouray County, COReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4983 Quarry Ln

Approved

Filed May 25, 2026 by Sam Calloway, Lakeside Backflow Testing · filed from phone

Report

Date of service
May 25, 2026
Assembly type
RP
Serial number
K376629
Size
3/4
Test gauge serial
G-8528
Gauge calibration date
Feb 7, 2026
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Calloway, current on the service date
  • All required fields present
  • Address matches parcel 091-72-01073
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4983 Quarry Ln
Owner: Blake Ellery
Parcel 091-72-01073