Ouray County, COReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4374 Sycamore Ct

Approved

Filed Mar 7, 2026 by Jamie Hollins, Clearwater Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Mar 7, 2026
Assembly type
RP
Serial number
W393637
Size
1
Test gauge serial
G-2481
Gauge calibration date
Jun 25, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Hollins, current on the service date
  • All required fields present
  • Address matches parcel 091-29-01157
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4374 Sycamore Ct
Owner: Parker Calloway
Parcel 091-29-01157