Backflow assembly test · Crossroads Apartments

Approved

Filed Nov 25, 2024 by Sam Calloway, Lakeside Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Nov 25, 2024
Assembly type
RP
Serial number
A591904
Size
1 1/2
Test gauge serial
G-3405
Gauge calibration date
May 9, 2024
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-29-01069
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1808 Laurel Ct
Owner: Ramirez Holdings LLC
Parcel 091-29-01069