Backflow assembly test · 1193 Spring Branch Ct
Needs reviewFiled Nov 15, 2026 by Sam Calloway, Lakeside Backflow Testing · filed from phone
Report
- Date of service
- Nov 15, 2026
- Assembly type
- RP
- Serial number
- W942406
- Size
- 3/4
- Test gauge serial
- G-3511
- Gauge calibration date
- Mar 23, 2026
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-18-01084
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
1193 Spring Branch Ct
Owner: Taylor Lindqvist
Parcel 091-18-01084