← Backflow review queue
Backflow assembly test · 6720 Fox Run Rd
ApprovedFiled Dec 12, 2024 by Jordan Ellery, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 12, 2024
- Assembly type
- PVB
- Serial number
- W131925
- Size
- 1
- Test gauge serial
- G-7385
- Gauge calibration date
- Jun 5, 2024
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Ellery, current on the service date
- All required fields present
- Address matches parcel 097-77-01161
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.