Backflow assembly test · 3115 Turkey Hill Dr
ApprovedFiled Jul 22, 2025 by Alex Wexler, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 22, 2025
- Assembly type
- RP
- Serial number
- A926732
- Size
- 3/4
- Test gauge serial
- G-3120
- Gauge calibration date
- Nov 8, 2024
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-68-01105
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.