Backflow assembly test · Two Rivers Diner
ApprovedFiled Sep 4, 2024 by Jordan Ellery, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 4, 2024
- Assembly type
- RP
- Serial number
- K107023
- Size
- 2
- Test gauge serial
- G-8571
- Gauge calibration date
- Jan 26, 2024
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-92-01270
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.