Pitkin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Bakery

Approved

Filed Mar 30, 2025 by Alex Benton, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Mar 30, 2025
Assembly type
RP
Serial number
A951320
Size
1 1/2
Test gauge serial
G-3907
Gauge calibration date
Aug 26, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 097-96-01208
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1978 Ridgeview Trl
Owner: Hollins Holdings LLC
Parcel 097-96-01208