Backflow assembly test · Riverside Market
ApprovedFiled Sep 17, 2025 by Alex Benton, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 17, 2025
- Assembly type
- DC
- Serial number
- Z212221
- Size
- 4
- Test gauge serial
- G-5960
- Gauge calibration date
- May 29, 2025
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-72-01344
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.