Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7268 Sycamore Ct

Approved

Filed Sep 22, 2025 by Taylor Vance, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Sep 22, 2025
Assembly type
RP
Serial number
Z167044
Size
3/4
Test gauge serial
G-4555
Gauge calibration date
Jul 17, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-63-01145
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7268 Sycamore Ct
Owner: Taylor Nguyen
Parcel 107-63-01145