Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Diner

Approved

Filed Jan 24, 2025 by Jamie Stroud, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Jan 24, 2025
Assembly type
RP
Serial number
Z954176
Size
2
Test gauge serial
G-3277
Gauge calibration date
Aug 12, 2024
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-17-01052
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

263 Spring Branch Dr
Owner: Ramirez Holdings LLC
Parcel 107-17-01052