← Backflow review queue
Backflow assembly test · Maple Leaf Diner
ApprovedFiled May 13, 2025 by Reese Whitcomb, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 13, 2025
- Assembly type
- RP
- Serial number
- Z430265
- Size
- 1 1/2
- Test gauge serial
- G-4111
- Gauge calibration date
- Nov 22, 2024
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-54-01010
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1601 Meadow Lark Trl
Owner: Kessler Holdings LLC
Parcel 107-54-01010