Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Car Wash

Approved

Filed Mar 31, 2026 by Alex Pruitt, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Mar 31, 2026
Assembly type
RP
Serial number
A324917
Size
1
Test gauge serial
G-8001
Gauge calibration date
Oct 18, 2025
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-16-01269
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

555 Old Church Dr
Owner: Ramirez Holdings LLC
Parcel 107-16-01269