Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4303 Sycamore Way

Approved

Filed Jun 26, 2024 by Taylor Vance, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Jun 26, 2024
Assembly type
RP
Serial number
A878433
Size
3/4
Test gauge serial
G-3284
Gauge calibration date
Dec 20, 2023
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-67-01183
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4303 Sycamore Way
Owner: Parker Wexler
Parcel 107-67-01183