Summit County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2656 Quarry Ct

Approved

Filed Apr 16, 2025 by Riley Pruitt, Ridge Backflow Testing · filed from phone

Report

Date of service
Apr 16, 2025
Assembly type
RP
Serial number
K121548
Size
3/4
Test gauge serial
G-3745
Gauge calibration date
Nov 8, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 117-66-01300
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2656 Quarry Ct
Owner: Jamie Calloway
Parcel 117-66-01300