Backflow assembly test · Golden Taqueria
ApprovedFiled Sep 23, 2023 by Jamie Hollins, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 23, 2023
- Assembly type
- DC
- Serial number
- B261014
- Size
- 4
- Test gauge serial
- G-8724
- Gauge calibration date
- Apr 3, 2023
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-12-01139
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.