Summit County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1092 Old Church Rd

Approved

Filed Jan 11, 2026 by Alex Whitcomb, Ridge Backflow Testing · filed from phone

Report

Date of service
Jan 11, 2026
Assembly type
RP
Serial number
B552450
Size
3/4
Test gauge serial
G-8104
Gauge calibration date
May 16, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 117-73-01229
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1092 Old Church Rd
Owner: Riley Pruitt
Parcel 117-73-01229