Backflow assembly test · 7255 Ridgeview Rd
ApprovedFiled Mar 17, 2025 by Avery Fairley, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 17, 2025
- Assembly type
- RP
- Serial number
- K112215
- Size
- 3/4
- Test gauge serial
- G-7976
- Gauge calibration date
- Aug 6, 2024
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-88-01082
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.