Backflow assembly test · 8629 Old Church Ln
ApprovedFiled Dec 21, 2023 by Alex Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 21, 2023
- Assembly type
- DC
- Serial number
- B744325
- Size
- 3/4
- Test gauge serial
- G-2082
- Gauge calibration date
- Sep 2, 2023
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-90-01272
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.