← Backflow review queue
Backflow assembly test · 9259 Stone Gate Way
ApprovedFiled Oct 20, 2026 by Jamie Hollins, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 20, 2026
- Assembly type
- DC
- Serial number
- K608516
- Size
- 1
- Test gauge serial
- G-6081
- Gauge calibration date
- May 2, 2026
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-37-01314
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9259 Stone Gate Way
Owner: Blake Nguyen
Parcel 117-37-01314