← Backflow review queue
Backflow assembly test · Maple Leaf Diner
ApprovedFiled Aug 20, 2025 by Blake Hollins, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Aug 20, 2025
- Assembly type
- RP
- Serial number
- Z143208
- Size
- 1
- Test gauge serial
- G-1256
- Gauge calibration date
- Oct 24, 2024
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 123-19-01247
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2261 Orchard Way
Owner: Nguyen Holdings LLC
Parcel 123-19-01247