Kent County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2044 Old Church Ln

Approved

Filed Jun 23, 2025 by Casey Fairley, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jun 23, 2025
Assembly type
RP
Serial number
K781795
Size
3/4
Test gauge serial
G-8001
Gauge calibration date
Feb 6, 2025
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-60-01091
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2044 Old Church Ln
Owner: Morgan Danner
Parcel 001-60-01091