Backflow assembly test · 4362 Quarry Way
ApprovedFiled Jun 25, 2025 by Alex Okafor, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Jun 25, 2025
- Assembly type
- DC
- Serial number
- A682387
- Size
- 3/4
- Test gauge serial
- G-9580
- Gauge calibration date
- Sep 25, 2024
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-34-01166
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.