Backflow assembly test · Golden Medical Offices
ApprovedFiled Jul 11, 2025 by Logan Ramirez, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 11, 2025
- Assembly type
- RP
- Serial number
- K962946
- Size
- 2
- Test gauge serial
- G-4141
- Gauge calibration date
- May 8, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-13-01068
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.