Backflow assembly test · 548 Spring Branch Ln

Approved

Filed May 17, 2025 by Avery Hollins, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
May 17, 2025
Assembly type
RP
Serial number
Z285300
Size
1
Test gauge serial
G-7941
Gauge calibration date
Feb 21, 2025
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-55-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.