← Backflow review queue
Backflow assembly test · Crossroads Bakery
ApprovedFiled Dec 12, 2024 by Alex Okafor, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Dec 12, 2024
- Assembly type
- RP
- Serial number
- B979960
- Size
- 2
- Test gauge serial
- G-3260
- Gauge calibration date
- Apr 12, 2024
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Relief valve opened at
- 4.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-83-01225
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9012 Sycamore Dr
Owner: Calloway Holdings LLC
Parcel 001-83-01225