Backflow assembly test · 3975 Quarry Ct
ApprovedFiled Dec 9, 2023 by Alex Okafor, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Dec 9, 2023
- Assembly type
- PVB
- Serial number
- K702250
- Size
- 1
- Test gauge serial
- G-4561
- Gauge calibration date
- Jul 24, 2023
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-82-01009
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.