Backflow assembly test · 819 Laurel Rd

Approved

Filed Jun 14, 2026 by Casey Fairley, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Jun 14, 2026
Assembly type
PVB
Serial number
B847607
Size
1
Test gauge serial
G-2865
Gauge calibration date
Sep 23, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-42-01156
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.