Kent County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Elementary School

Approved

Filed Oct 18, 2025 by Alex Okafor, Keystone Backflow Testing · filed from phone

Report

Date of service
Oct 18, 2025
Assembly type
RP
Serial number
B898020
Size
4
Test gauge serial
G-5990
Gauge calibration date
Apr 6, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-90-01347
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7071 Stone Gate Ct
Owner: Lindqvist Holdings LLC
Parcel 001-90-01347