← Backflow review queue
Backflow assembly test · Golden Grill
ApprovedFiled Dec 16, 2025 by Rowan Hollins, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 16, 2025
- Assembly type
- RP
- Serial number
- K162726
- Size
- 1 1/2
- Test gauge serial
- G-8089
- Gauge calibration date
- Mar 10, 2025
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-38-01326
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4879 Cedar Hollow Ln
Owner: Harlow Holdings LLC
Parcel 003-38-01326