Backflow assembly test · Riverside Self Storage

Approved

Filed Nov 23, 2024 by Rowan Hollins, Northstar Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Nov 23, 2024
Assembly type
RP
Serial number
A570025
Size
1 1/2
Test gauge serial
G-9623
Gauge calibration date
Oct 21, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-97-01167
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4176 Meadow Lark Dr
Owner: Whitcomb Holdings LLC
Parcel 003-97-01167