New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Medical Offices

Approved

Filed Dec 12, 2025 by Blake Harlow, Ridge Backflow Testing · filed from phone

Report

Date of service
Dec 12, 2025
Assembly type
RP
Serial number
W758093
Size
4
Test gauge serial
G-9584
Gauge calibration date
Jul 14, 2025
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-47-01180
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7763 Orchard Ln
Owner: Okafor Holdings LLC
Parcel 003-47-01180