← Backflow review queue
Backflow assembly test · Hilltop Apartments
ApprovedFiled Jan 2, 2026 by Logan Nguyen, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 2, 2026
- Assembly type
- RP
- Serial number
- K265679
- Size
- 2
- Test gauge serial
- G-5083
- Gauge calibration date
- Apr 27, 2025
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-96-01322
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1385 Stone Gate Ln
Owner: Okafor Holdings LLC
Parcel 003-96-01322