Backflow assembly test · Crossroads Grill
ApprovedFiled Oct 4, 2024 by Rowan Hollins, Northstar Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 4, 2024
- Assembly type
- RP
- Serial number
- W443827
- Size
- 4
- Test gauge serial
- G-7096
- Gauge calibration date
- Jul 12, 2024
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-37-01103
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.